Key Features

~

Layered password protection for setup changes

Multiple event tracking capability for up to 128 independent sensor circuits

Universal power supply for 110/220 Vac 50/60 Hz (24-volt option available)

Non-volatile memory for event history, setup and network configuration

Easy setup and simple operation

To monitor and manage multiple sensors and devices, the TTDM-128 unit is simple to setup. Additionally, it can monitor in-depth data and analytics on any potential leaks or risks to the environment.

TTDM-128

The TTDM-128 has the leak location on the front panel of the monitoring host that acts as the master module for all of the TTSIM up to 128 independent sensor circuits and has four holes for secure mounting in business facilities. Allowing any sensor circuit to identify, locate, and track leaks separately from any other circuits linked to the TTDM-128.

W

Distinctive front panel LED display

TTDM-128 front panel LED display can track or locate issues and minimize downtime by immediately identifying real-time problems as they arise, ensuring that business facilities can operate properly and remotely.

Product Information

Specification

Operation Voltage22 to 26 Vac, 3 W 12 Vdc +/– 10%, 2 W
92 to 132 Vac, 3 W 24 Vdc +/– 10%, 2 W
216 to 253 Vac, 3 W
Operating Temperature: 0°C to 50°C
Operating Humidity5% to 95% non-condensing
Communication protocolModbus®, OptoMux™ or Johnson Controls Metasys™
Network ConfigurationRS-485 two wire network, 9600 baud, addressable from 1 to 127
Maximum length of sensing cable150 m (5000 ft)
Precision0.5% of sensor length ± 0.6 m (2 ft)
Dimension86 x 70 x 58 mm